Alarms
The
Adtech Model ACA 142 AC Current/Voltage Dual Alarm
accepts a standard AC current/voltage input signal and provides two (2) SPDT
relay contact output setpoints rated at 10 amps; 30 VDC, or 250 VAC resistive.
An exclusive feature is that the input can be configured to accept either an
"average" input (standard) or true rms input response (specify).
Integral dual color LEDs provide green indication for normal conditions and red
indication on alarm setpoint independent of relay coil power.
The
Adtech Model DCA 114 100 Series DC/Current Single Alarm
accepts a standard process DC current/voltage input signal and provides a DPDT
relay contact output setpoint rated at 10 amps; 30 VDC or 250 VAC resistive.
A 24 VDC at 35 mA output is provided as standard for powering a loop
transmitter.
Integral dual color LEDs provide green indication for normal conditions and red
indication on alarm setpoint independent of relay coil.
The Adtech Model DCA 115 100 Series DC/Current Dual Alarm
(see DCA 114 picture) accepts a standard process DC
current/voltage input signal and provides two SPDT relay contact output
setpoints rated at 10 amps; 30 VDC, or 250 VAC resistive.
A 24 VDC at 35 mA output is provided as standard for powering a loop
transmitter.
Integral dual color LEDs provide green indication for normal conditions and red
indication on alarm setpoint independent of relay coil power.
The
Adtech Model RBA 174 Resistance Bulb Single Alarm
accepts all standard 2, 3, & 4 wire RTD input types and provides a DPDT
relay contact output setpoint rated at 10 amps; 30 VDC or 250 VAC resistive.
A 24 VDC at 35 mA output is provided as standard for powering a loop
transmitter.
Integral dual color LEDs provide green indication for normal conditions and red
indication on alarm setpoint independent of relay coil.
The Adtech Model RBA 175 Resistance Bulb Dual Alarm
(see RBA-174 picture) accepts all standard 2, 3, & 4 wire RTD type inputs
and provides two SPDT relay contact output setpoints rated at 10 amps; 30 VDC,
or 250 VAC resistive.
A 24 VDC at 35 mA output is provided as standard for powering a loop
transmitter.
Integral dual color LEDs provide green indication for normal conditions and red
indication on alarm setpoint independent of relay coil.
The
Adtech Model TCA 104 Thermocouple Single Alarm accepts
any standard ISA thermocouple type input and provides a DPDT relay contact
output setpoint rated at 10 amps; 30 VDC or 250 VAC resistive.
A 24 VDC at 35 mA output is provided as standard for powering a loop
transmitter.
Integral dual color LEDs provide green indication for normal conditions and red
indication on alarm setpoint independent of relay coil.
The Adtech Model TCA 105 Thermocouple Dual Alarm
(see TCA-104 picture) accepts any standard ISA thermocouple type input and
provides two SPDT relay contact output setpoints rated at 10 amps; 30 VDC or 250
VAC resistive.
A 24 VDC at 35 mA output is provided as standard for powering a loop
transmitter.
Integral dual color LEDs provide green indication for normal conditions and red
indication on alarm setpoint independent of relay coil.
The
Adtech Model CLA 114 Loop Powered Trip Alarm accepts a
standard process signal of 4-20 mA input and provides a SPDT relay contact
output. A DPDT relay contact is available when specifying Option O49.
The CLA 114 does not require a separate DC or AC power supply source like other
conventional alarms.
It has a 0-100% adjustable set point and a 0.5% fixed dead band. Option O46S
provides a 1-100% adjustable dead band.
Two indicating LEDs are standard to the CLA 114.
DIN rail mounting is supplied as standard. Surface mount (Option H26) or snap
track mount (Option H25) are available at no extra cost (specify).
The
Adtech Model DCA 514 AC Powered DC/Current Single Alarm
comes in a compact DIN package providing mounting efficiency and ease of wiring.
The small size makes it an ideal replacement for the typical powered single
alarm.
The DCA 514 accepts a standard process DC current/voltage input signal and
provides a user configurable SPDT relay contact output setpoint rated at 10
amps; 30 VDC, or 250 VAC resistive.
An isolated 24 VDC output at 30 mA is provided as standard for powering a loop
transmitter.
Integral dual color LEDs provide green indication for normal conditions and red
indication on alarm and is independent of relay coil power.
Product
Data Bulletin